| Plan Review Notes For Permit 16100277 |
| Permit Number |
16100277 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-21 12:26:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE SECURITY VESTIBULE PERMIT IS EXPIRED. THE PLAN | | | SHOWS THIS AS EXISTING, BUT IT IS EXISTING (FOR | | | BUILDING CODE PURPOSES) ONLY IF IT WAS LEGALLY | | | PERMITTED, CONSTRUCTED AS PERMITTED, AND FINALED. THE | | | PLAN SHOWS THAT THE CONSTRUCTION IS NOT CONSISTENT WITH | | | THE ISSUED PERMIT, DOES NOT APPEAR TO COMPLY WITH | | | ACCESSIBILITY MANEUVERING CLEARANCE REQUIREMENT ON THE | | | PULL SIDE, AND NO BUILDING INSPECTIONS WERE SCHEDULED | | | (ONLY FIRE INSPECTIONS). | | | | | | EITHER APPLY FOR A SEPARATE PERMIT FOR THE VESTIBULE | | | WORK, OR INCORPORATE THAT WORK INTO THIS PERMIT. SEE | | | EXPIRED PERMIT 14020726. YOU MAY OBTAIN A COPY OF THE | | | PLAN FOR THAT PERMIT BY SUBMITTING A REQUEST TO | | | [email protected]. | | | | | | 2. UNNUMBERED DOOR WHICH SERVES THE BACK AREA, SHOW THE | | | 18IN PULL SIDE MANEUVERING CLEARANCE FBC 5TH EDITION | | | ACCESSIBILITY 404.2.4.1. | | | | | | 3. SHEET A4.1 REFERS TO FBC 2007 IN MORE THAN ONE | | | LOCATION, REVISE. | | | | | | 4. PROVIDE THE PRODUCT APPROVAL FOR THE NEW DRIVE UP | | | ATM. PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF | | | RECORD, FBC 107. | | | | | | 5. PLAN LACKS WIND DESIGN CRITERIA, FBC 1603.4.1., ADD | | | TO PLAN. | | | | | | 6. SEE PLUMBING COMMENTS AND REVISE PLAN ACCORDINGLY. | | | | | | | | | | | | | | | |
|