2016-10-21 12:26:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SECURITY VESTIBULE PERMIT IS EXPIRED. THE PLAN
 SHOWS THIS AS EXISTING, BUT IT IS EXISTING (FOR
 BUILDING CODE PURPOSES) ONLY IF IT WAS LEGALLY
 PERMITTED, CONSTRUCTED AS PERMITTED, AND FINALED. THE
 PLAN SHOWS THAT THE CONSTRUCTION IS NOT CONSISTENT WITH
 THE ISSUED PERMIT, DOES NOT APPEAR TO COMPLY WITH
 ACCESSIBILITY MANEUVERING CLEARANCE REQUIREMENT ON THE
 PULL SIDE, AND NO BUILDING INSPECTIONS WERE SCHEDULED
 (ONLY FIRE INSPECTIONS).
  
 EITHER APPLY FOR A SEPARATE PERMIT FOR THE VESTIBULE
 WORK, OR INCORPORATE THAT WORK INTO THIS PERMIT. SEE
 EXPIRED PERMIT 14020726. YOU MAY OBTAIN A COPY OF THE
 PLAN FOR THAT PERMIT BY SUBMITTING A REQUEST TO
 [email protected].
  
 2. UNNUMBERED DOOR WHICH SERVES THE BACK AREA, SHOW THE
 18IN PULL SIDE MANEUVERING CLEARANCE FBC 5TH EDITION
 ACCESSIBILITY 404.2.4.1.
  
 3. SHEET A4.1 REFERS TO FBC 2007 IN MORE THAN ONE
 LOCATION, REVISE.
  
 4. PROVIDE THE PRODUCT APPROVAL FOR THE NEW DRIVE UP
 ATM. PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC 107.
  
 5. PLAN LACKS WIND DESIGN CRITERIA, FBC 1603.4.1., ADD
 TO PLAN.
  
 6. SEE PLUMBING COMMENTS AND REVISE PLAN ACCORDINGLY.
  
  
  
  
  