Plan Review Notes
Plan Review Notes For Permit 16100266
Permit Number 16100266
Review Stop M
Sequence Number 3
Notes
Date Text
2017-01-04 11:13:543RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100266
 1/4/17
  
 1) THE RTU CURB ENGINEERING SUBMITTAL MUST BEAR AN
 ORIGINAL SEAL AND SIGNATURE FROM THE CERTIFYING P.E.
 JOHN BUEROSE- SECTION 61G15- 23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 2) THE REVISED ENERGY FORM C402 DOES NOT BEAR THE
 SIGNATURE OF THE OWNER/AGENT.
  
 3) PROVIDE A SUBMITTAL FOR THE C02 SENSORS. IT APPEARS
 THAT ONLY ONE SENSOR IS BEING INSTALLED IN THE SPACE
 WHICH MAY BE INADEQUATE COVERAGE BASED ON SQUARE
 FOOTAGE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  