| 2017-01-19 14:46:49 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16100266 |
| | ADD: 2471 OKEECHOBEE BLVD. SUITE # 7 |
| | CONT: ARGOS BUILDERS LLC |
| | CONTACT: RAMON CASTRO |
| | TEL: 407-877-3009 EXT 106 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. JAN. 19/ 2017 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | 4)3RD SEMI-COMPLIED. 2014 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS. |
| | SEE COMMENT # 6. |
| | |
| | |
| | 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6)3RD REQUEST. |
| | 4X FEE NOTICE!!!!! |
| | FLORIDA STATUTE 553.80(2)(B) WITH RESPECT TO EVALUATION |
| | OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL |
| | GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE |
| | COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A |
| | PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE |
| | THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE |
| | VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH |
| | REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE |
| | PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | SUBMITTED WERE COPIES OF SIGNED AND SEALED CARRIER |
| | MOUNTING OF THE RTU TO THE ROOF TOP CURB. PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY |
| | THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| | PROFESSIONAL AFFIXED TO THE DOCUMENT. F. S. 471.025 |
| | THE SUBMITTED CARRIER DOCUMENTS SHOWS THE PROCEDURE OF |
| | MOUNTING THE RTU TO THE CARRIER CURB BUT THERE IS NO |
| | DOCUMENTS SHOWING HOW THE CURB IS TO BE SECURED TO THE |
| | ROOF FRAMING SYSTEM TO BE SECURED TO THE MWFRS (MAIN |
| | WIND FORCE RESISTING SYSTEM. 2014 FBC-B 1604.4 |
| | ANALYSIS. 2014 FBC-M- 301.15 WIND RESISTANCE |
| | 1ST ROUND OF COMMENTS. SHEET M1 NOTE # 1 INDICATES TO |
| | REPLACE ALL ROOF TOP UNITS. SHEET M3 SHOWS A ROOF TOP |
| | A/C CURB BUT NO INFORMATION AS TO THE ATTACHING OF THE |
| | CURB TO THE ROOF FRAMING PART OF THE (MWFRS) MAIN WIND |
| | FORCE RESISTING SYSTEM. PLEASE PROVIDE ANCHORING OF THE |
| | CURB AND RTU TO RESIST THE MOMENT OF OVERTURNING. |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |