| Plan Review Notes For Permit 16100266 |
| Permit Number |
16100266 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-05 09:14:59 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100266 | | | 12/5/16 | | | | | | 1) COMMENTS #5 & 6 FROM THE 1ST REVIEW STILL EXIST- | | | PLEASE COMPLY. | | | | | | 2) SHEET M1.0: SHOW THE LOCATIONS OF THE CO2 SENSORS ON | | | THE FLOOR PLAN- KEYED NOTE #11. | | | | | | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100266 | | | 10/20/16 | | | | | | 5) M3.0: THE RTU MOUNTING DETAIL DOES NOT INDICATE HOW | | | THE CURB WILL BE ATTACHED TO THE STRUCTURE, AND THERE | | | ARE NO STRUCTURAL DETAILS FOR THAT ATTACHMENT ON THE | | | ARCHITECTURAL OR STRUCTURAL PLAN SHEETS. PLEASE PROVIDE | | | COMPLETE INSTALLATION DETAILS AND COMPLETE DESIGN | | | CRITERIA- EXPOSURE CATEGORY, IMPORTANCE FACTOR, HEIGHT | | | AND ADJUSTMENT COEFFICIENT, AND DESIGN PRESSURES. | | | | | | 6) THE ENERGY COMPLIANCE FORM C402-2014 IS NOT FILLED | | | OUT CORRECTLY. PLEASE REMOVE "SEE ATTACHMENT" AND | | | PROVIDE THE REQUIRED AC AND HEATING SYSTEM DATA IN THE | | | APPROPRIATE BOXES UNDER THE COLUMN TITLED "TYPE", AND | | | THE EFFICIENCY RATINGS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|