Plan Review Notes
Plan Review Notes For Permit 16100266
Permit Number 16100266
Review Stop B
Sequence Number 2
Notes
Date Text
2016-12-09 15:38:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16100266
 ADD: 2471 OKEECHOBEE BLVD. SUITE # 7
 CONT: TBD/ TO BE DETERMINED
 TEL: NO CONTACT INFO
 E-MAIL: NO CONTACT INFO
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. DEC. 09/ 2016
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SEMI-COMPLIED. SHEET A-7.3 DETAIL 2 SHOWS A 42 INCH
 GUARDRAIL/ HANDRAIL SYSTEM. PLEASE NOTE THERE IS NO
 HANDRAIL SHOWN IN THE DETAIL. THE 2014 FBC-B SECTION
 1010.9 REQUIRES HANDRAILS ON BOTH SIDES WHEN THE RISE
 IS GREATER THAN OF THE RAMP IS GREATER THAN 6 INCHES.
 SECTION 1012.2 THE HANDRAIL HEIGHT IS BETWEEN 34 AND 38
 INCHES.
 1012.6 HANDRAIL EXTENSIONS. HANDRAILS SHALL RETURN TO A
 WALL, GUARD OR THE WALKING SURFACE OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN ADJACENT STAIR FLIGHT
 OR RAMP RUN. AT RAMPS WHERE HANDRAILS ARE NOT
 CONTINUOUS BETWEEN RUNS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY ABOVE THE LANDING 12 INCHES (305 MM)
 MINIMUM BEYOND THE TOP AND BOTTOM OF RAMP RUNS. THE
 EXTENSIONS OF HANDRAILS SHALL BE IN THE SAME DIRECTION
 OF THE STAIR FLIGHTS AT STAIRWAYS AND THE RAMP RUNS AT
 RAMPS.
 1ST ROUND COMMENTS. SHEET A-7.0 SHOWS A NEW SIDE DOOR
 AND ACCESS RAMP. SHEET A-7.3 DETAIL A CUT SECTION
 THROUGH THE LENGTH OF THE RAMP. THE PLANS DO NOT
 PROVIDE THE WIDTH OF THE RAMP NOR INDICATE A TURNING
 RADIUS INCOMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE
 405.7.4 CHANGE IN DIRECTION.
  
 4) SEMI-COMPLIED. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS .
 CECO APPROVAL FROM UL IS AN OUT OF DATE 2006 REPORT,
 AND NO INSTALLATION INSTRUCTIONS FOR INSTALLATION WERE
 PROVIDE WITH THE REPORT.
  
 (C) PANEL WALLS: STOREFRONTS WINDOW & DOOR COMPLIED.
  
 (D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS/
 ROOF TOP EXHAUST FANS. SEE COMMENT # 6.
  
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 2ND REQUEST. SUBMITTED WERE COPIES OF SIGNED AND
 SEALED CARRIER MOUNTING OF THE RTU TO THE ROOF TOP
 CURB. PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. F. S.
 471.025
 THE SUBMITTED CARRIER DOCUMENTS SHOWS THE PROCEDURE OF
 MOUNTING THE RTU TO THE CARRIER CURB BUT THERE IS NO
 DOCUMENTS SHOWING HOW THE CURB IS TO BE SECURED TO THE
 ROOF FRAMING SYSTEM TO BE SECURED TO THE MWFRS (MAIN
 WIND FORCE RESISTING SYSTEM. 2014 FBC-B 1604.4
 ANALYSIS. 2014 FBC-M- 301.15 WIND RESISTANCE
 1ST ROUND OF COMMENTS. SHEET M1 NOTE # 1 INDICATES TO
 REPLACE ALL ROOF TOP UNITS. SHEET M3 SHOWS A ROOF TOP
 A/C CURB BUT NO INFORMATION AS TO THE ATTACHING OF THE
 CURB TO THE ROOF FRAMING PART OF THE (MWFRS) MAIN WIND
 FORCE RESISTING SYSTEM. PLEASE PROVIDE ANCHORING OF THE
 CURB AND RTU TO RESIST THE MOMENT OF OVERTURNING.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  