| 2016-10-20 11:56:53 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16100266 |
| | 10/20/16 |
| | |
| | 1) SHEET M2.0: THE OUTSIDE AIR CALCULATIONS SHOW A |
| | SHORTAGE OF 198 CFMS FOR THE RTU'S SUPPLYING AIR TO THE |
| | SALES AREA. |
| | |
| | 2) M1.0: PLEASE PROVIDE THE FLEX DUCT SIZES OR RELOCATE |
| | THE SCHEDULE ON SHEET M2.0 TO M1.0 |
| | |
| | 3) M1.0: THE 6" TRANSFER DUCT AT THE VESTIBULE/WORK |
| | ROOM IS UNDERSIZED PER SECTION 601.5. |
| | |
| | 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED |
| | CLEARANCE DISTANCE MEASUREMENTS FROM AIR INTAKES TO |
| | EXHAUST OUTLETS, AND EQUIPMENT TO ROOF EDGES. A) |
| | CLARIFY HOW ACCESS TO THE ROOFTOP MECHANICAL EQUIPMENT |
| | IS BEING PROVIDED- SECTION 306.5. |
| | |
| | 5) M3.0: THE RTU MOUNTING DETAIL DOES NOT INDICATE HOW |
| | THE CURB WILL BE ATTACHED TO THE STRUCTURE, AND THERE |
| | ARE NO STRUCTURAL DETAILS FOR THAT ATTACHMENT ON THE |
| | ARCHITECTURAL OR STRUCTURAL PLAN SHEETS. PLEASE PROVIDE |
| | COMPLETE INSTALLATION DETAILS AND COMPLETE DESIGN |
| | CRITERIA- EXPOSURE CATEGORY, IMPORTANCE FACTOR, HEIGHT |
| | AND ADJUSTMENT COEFFICIENT, AND DESIGN PRESSURES. |
| | |
| | 6) THE ENERGY COMPLIANCE FORM C402-2014 IS NOT FILLED |
| | OUT CORRECTLY. PLEASE REMOVE "SEE ATTACHMENT" AND |
| | PROVIDE THE REQUIRED AC AND HEATING SYSTEM DATA IN THE |
| | APPROPRIATE BOXES UNDER THE COLUMN TITLED "TYPE", AND |
| | THE EFFICIENCY RATINGS. |
| | |