Plan Review Notes
Plan Review Notes For Permit 16100266
Permit Number 16100266
Review Stop M
Sequence Number 1
Notes
Date Text
2016-10-20 11:56:531ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100266
 10/20/16
  
 1) SHEET M2.0: THE OUTSIDE AIR CALCULATIONS SHOW A
 SHORTAGE OF 198 CFMS FOR THE RTU'S SUPPLYING AIR TO THE
 SALES AREA.
  
 2) M1.0: PLEASE PROVIDE THE FLEX DUCT SIZES OR RELOCATE
 THE SCHEDULE ON SHEET M2.0 TO M1.0
  
 3) M1.0: THE 6" TRANSFER DUCT AT THE VESTIBULE/WORK
 ROOM IS UNDERSIZED PER SECTION 601.5.
  
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FROM AIR INTAKES TO
 EXHAUST OUTLETS, AND EQUIPMENT TO ROOF EDGES. A)
 CLARIFY HOW ACCESS TO THE ROOFTOP MECHANICAL EQUIPMENT
 IS BEING PROVIDED- SECTION 306.5.
  
 5) M3.0: THE RTU MOUNTING DETAIL DOES NOT INDICATE HOW
 THE CURB WILL BE ATTACHED TO THE STRUCTURE, AND THERE
 ARE NO STRUCTURAL DETAILS FOR THAT ATTACHMENT ON THE
 ARCHITECTURAL OR STRUCTURAL PLAN SHEETS. PLEASE PROVIDE
 COMPLETE INSTALLATION DETAILS AND COMPLETE DESIGN
 CRITERIA- EXPOSURE CATEGORY, IMPORTANCE FACTOR, HEIGHT
 AND ADJUSTMENT COEFFICIENT, AND DESIGN PRESSURES.
  
 6) THE ENERGY COMPLIANCE FORM C402-2014 IS NOT FILLED
 OUT CORRECTLY. PLEASE REMOVE "SEE ATTACHMENT" AND
 PROVIDE THE REQUIRED AC AND HEATING SYSTEM DATA IN THE
 APPROPRIATE BOXES UNDER THE COLUMN TITLED "TYPE", AND
 THE EFFICIENCY RATINGS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719