 PERMIT #16100266
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS INDICATE AN ADDRESS OF "123 MAIN STREET, ANYTOWN
 US 12345."
  
 SHEET A-2.0: THE OCCUPANT LOAD BREAK DOWN CHART IS
 INCORRECT. FOR EXAMPLE 7,257 SQ.FT. WOULD RESULT IN AN
 OCCUPANT LOAD OF 241 (30 SQ.FT. PER PERSON) NOT 139.
  
 SHEET E-2.0: ONLY TWO EXIT SIGNS HAVE BEEN PROVIDED FOR
 THE +7,000 SQ.FT. MERCANTILE FLOOR PLAN.
  
 SHEET E-3.0: THE REAR DOOR (DOOR TAG 5) INDICATES THE
 INSTALLATION OF A DOOR BELL. WHAT IS THE FUNCTION OF
 THIS BELL? THIS DOOR IS AN EXIT ACCESS DOOR TO THE
 SECOND BUILDING EXIT AND IS NOT PERMITTED TO BE LOCKED
 OR RESTRICTED.
  
 FIRE ALARM: I BELIEVE THE ENTIRE BUILDING IS PROTECTED
 BY A FIRE ALARM SYSTEM; HOWEVER, THE PLANS DO NOT SHOW
 ANY FIRE ALARM NOTIFICATION DEVICES.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  