| Plan Review Notes For Permit 16100266 |
| Permit Number |
16100266 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-21 11:14:08 | 2471 OKEECHOBEE BOULEVARD -SUITE 7 | | | PERMIT #16100266 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS INDICATE AN ADDRESS OF "123 MAIN STREET, ANYTOWN | | | US 12345." | | | | | | SHEET A-2.0: THE OCCUPANT LOAD BREAK DOWN CHART IS | | | INCORRECT. FOR EXAMPLE 7,257 SQ.FT. WOULD RESULT IN AN | | | OCCUPANT LOAD OF 241 (30 SQ.FT. PER PERSON) NOT 139. | | | | | | SHEET E-2.0: ONLY TWO EXIT SIGNS HAVE BEEN PROVIDED FOR | | | THE +7,000 SQ.FT. MERCANTILE FLOOR PLAN. | | | | | | SHEET E-3.0: THE REAR DOOR (DOOR TAG 5) INDICATES THE | | | INSTALLATION OF A DOOR BELL. WHAT IS THE FUNCTION OF | | | THIS BELL? THIS DOOR IS AN EXIT ACCESS DOOR TO THE | | | SECOND BUILDING EXIT AND IS NOT PERMITTED TO BE LOCKED | | | OR RESTRICTED. | | | | | | FIRE ALARM: I BELIEVE THE ENTIRE BUILDING IS PROTECTED | | | BY A FIRE ALARM SYSTEM; HOWEVER, THE PLANS DO NOT SHOW | | | ANY FIRE ALARM NOTIFICATION DEVICES. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|