Plan Review Notes
Plan Review Notes For Permit 16100266
Permit Number 16100266
Review Stop E
Sequence Number 1
Notes
Date Text
2016-10-25 09:15:28INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT
 ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY
 REGULATORY AGENCIES.
 3. ADDRESS FIRE COMMENTS RELATED TO ELECTRICAL
 EMERGENCY LIGHTING. FBC 107.3.5
 4. PLEASE CLARIFY IF EXISTING RISER SHOWN HAS OTHER
 MAINS, ARE YOU JUST SHOWING THE 400AMP FOR SHOE
 CARNIVAL STORE? 800AMP TO BE SUFFICIENT TO CARRY ALL
 LOADS. PLEASE CLARIFY
 5. CORRECT TYPO AT PANEL SCHEDULE FOR PANEL P. IS IT A
 225MLO OR 100AMPMLO? RISER AND PANEL DO NOT CORRELATE.
 FBC 107.3.5
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  