2016-10-18 13:28:34THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PROVIDE WARNING SIGNS AND INSTRUCTIONS PER NFPA
 2001, CHAPTER 4
  
 4.3.5 OPERATING ALARMS AND INDICATORS.
 4.3.5.1 ALARMS OR INDICATORS OR BOTH SHALL BE USED TO
 INDICATE THE OPERATION OF THE SYSTEM, HAZARDS TO
 PERSONNEL, OR FAILURE OF ANY SUPERVISED DEVICE. THE
 TYPE (AUDIBLE, VISUAL, OR OLFACTORY), NUMBER, AND
 LOCATION OF THE DEVICES SHALL BE SUCH THAT THEIR
 PURPOSE IS SATISFACTORILY ACCOMPLISHED. THE EXTENT AND
 TYPE OF ALARMS OR INDICATOR EQUIPMENT OR BOTH SHALL BE
 APPROVED.
  
 4.3.5.2 AUDIBLE AND VISUAL PRE-DISCHARGE ALARMS SHALL
 BE PROVIDED WITHIN THE PROTECTED AREA TO GIVE POSITIVE
 WARNING OF IMPENDING DISCHARGE. THE OPERATION OF THE
 WARNING DEVICES SHALL BE CONTINUED AFTER AGENT
 DISCHARGE UNTIL POSITIVE ACTION HAS BEEN TAKEN TO
 ACKNOWLEDGE THE ALARM AND PROCEED WITH APPROPRIATE
 ACTION.
  
 4.3.5.3* ABORT SWITCHES, WHERE PROVIDED, SHALL BE
 LOCATED WITHIN THE PROTECTED AREA AND SHALL BE LOCATED
 NEAR THE MEANS OF EGRESS FOR THE AREA. THE ABORT SWITCH
 SHALL BE OF A TYPE THAT REQUIRES CONSTANT MANUAL
 PRESSURE TO CAUSE ABORT. IN ALL CASES, THE NORMAL
 MANUAL CONTROL AND THE MANUAL EMERGENCY CONTROL SHALL
 OVERRIDE THE ABORT FUNCTION. OPERATION OF THE ABORT
 FUNCTION SHALL RESULT IN BOTH AUDIBLE AND DISTINCT
 VISUAL INDICATION OF SYSTEM IMPAIRMENT. THE ABORT
 SWITCH SHALL BE CLEARLY RECOGNIZABLE FOR THE PURPOSE
 INTENDED.
  
 4.3.5.4 ALARMS INDICATING FAILURE OF SUPERVISED DEVICES
 OR EQUIPMENT SHALL GIVE PROMPT AND POSITIVE INDICATION
 OF ANY FAILURE AND SHALL BE DISTINCTIVE FROM ALARMS
 INDICATING OPERATION OR HAZARDOUS CONDITIONS.
  
 4.3.5.5 WARNING AND INSTRUCTION SIGNS AT ENTRANCES TO
 AND INSIDE PROTECTED AREAS SHALL BE PROVIDED.
  
 4.3.5.5.1 WARNING AND SAFETY INSTRUCTION SIGNS SHALL BE
 LOCATED SUCH THAT THEY WILL BE READILY VISIBLE TO
 PERSONNEL IN THE AREA WHERE THE CLEAN AGENT DESIGN
 CONCENTRATION EXCEEDS THAT APPROVED FOR USE IN NORMALLY
 OCCUPIED SPACES. THE SAFETY SIGN FORMAT AND COLOR AND
 THE LETTER STYLE OF THE SIGNAL WORDS SHALL BE IN
 ACCORDANCE WITH ANSI Z535.
  
 4.3.5.5.2 WARNING AND SAFETY INSTRUCTION SIGNS SHALL BE
 LOCATED OUTSIDE EACH ENTRANCE TO CLEAN AGENT CYLINDER
 STORAGE ROOMS. THE SAFETY SIGN FORMAT AND COLOR AND THE
 LETTER STYLE OF THE SIGNAL WORDS SHALL BE IN ACCORDANCE
 WITH ANSI Z535.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  