| Date |
Text |
| 2016-10-18 13:28:34 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1) PROVIDE WARNING SIGNS AND INSTRUCTIONS PER NFPA |
| | 2001, CHAPTER 4 |
| | |
| | 4.3.5 OPERATING ALARMS AND INDICATORS. |
| | 4.3.5.1 ALARMS OR INDICATORS OR BOTH SHALL BE USED TO |
| | INDICATE THE OPERATION OF THE SYSTEM, HAZARDS TO |
| | PERSONNEL, OR FAILURE OF ANY SUPERVISED DEVICE. THE |
| | TYPE (AUDIBLE, VISUAL, OR OLFACTORY), NUMBER, AND |
| | LOCATION OF THE DEVICES SHALL BE SUCH THAT THEIR |
| | PURPOSE IS SATISFACTORILY ACCOMPLISHED. THE EXTENT AND |
| | TYPE OF ALARMS OR INDICATOR EQUIPMENT OR BOTH SHALL BE |
| | APPROVED. |
| | |
| | 4.3.5.2 AUDIBLE AND VISUAL PRE-DISCHARGE ALARMS SHALL |
| | BE PROVIDED WITHIN THE PROTECTED AREA TO GIVE POSITIVE |
| | WARNING OF IMPENDING DISCHARGE. THE OPERATION OF THE |
| | WARNING DEVICES SHALL BE CONTINUED AFTER AGENT |
| | DISCHARGE UNTIL POSITIVE ACTION HAS BEEN TAKEN TO |
| | ACKNOWLEDGE THE ALARM AND PROCEED WITH APPROPRIATE |
| | ACTION. |
| | |
| | 4.3.5.3* ABORT SWITCHES, WHERE PROVIDED, SHALL BE |
| | LOCATED WITHIN THE PROTECTED AREA AND SHALL BE LOCATED |
| | NEAR THE MEANS OF EGRESS FOR THE AREA. THE ABORT SWITCH |
| | SHALL BE OF A TYPE THAT REQUIRES CONSTANT MANUAL |
| | PRESSURE TO CAUSE ABORT. IN ALL CASES, THE NORMAL |
| | MANUAL CONTROL AND THE MANUAL EMERGENCY CONTROL SHALL |
| | OVERRIDE THE ABORT FUNCTION. OPERATION OF THE ABORT |
| | FUNCTION SHALL RESULT IN BOTH AUDIBLE AND DISTINCT |
| | VISUAL INDICATION OF SYSTEM IMPAIRMENT. THE ABORT |
| | SWITCH SHALL BE CLEARLY RECOGNIZABLE FOR THE PURPOSE |
| | INTENDED. |
| | |
| | 4.3.5.4 ALARMS INDICATING FAILURE OF SUPERVISED DEVICES |
| | OR EQUIPMENT SHALL GIVE PROMPT AND POSITIVE INDICATION |
| | OF ANY FAILURE AND SHALL BE DISTINCTIVE FROM ALARMS |
| | INDICATING OPERATION OR HAZARDOUS CONDITIONS. |
| | |
| | 4.3.5.5 WARNING AND INSTRUCTION SIGNS AT ENTRANCES TO |
| | AND INSIDE PROTECTED AREAS SHALL BE PROVIDED. |
| | |
| | 4.3.5.5.1 WARNING AND SAFETY INSTRUCTION SIGNS SHALL BE |
| | LOCATED SUCH THAT THEY WILL BE READILY VISIBLE TO |
| | PERSONNEL IN THE AREA WHERE THE CLEAN AGENT DESIGN |
| | CONCENTRATION EXCEEDS THAT APPROVED FOR USE IN NORMALLY |
| | OCCUPIED SPACES. THE SAFETY SIGN FORMAT AND COLOR AND |
| | THE LETTER STYLE OF THE SIGNAL WORDS SHALL BE IN |
| | ACCORDANCE WITH ANSI Z535. |
| | |
| | 4.3.5.5.2 WARNING AND SAFETY INSTRUCTION SIGNS SHALL BE |
| | LOCATED OUTSIDE EACH ENTRANCE TO CLEAN AGENT CYLINDER |
| | STORAGE ROOMS. THE SAFETY SIGN FORMAT AND COLOR AND THE |
| | LETTER STYLE OF THE SIGNAL WORDS SHALL BE IN ACCORDANCE |
| | WITH ANSI Z535. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |