| Plan Review Notes For Permit 16100216 |
| Permit Number |
16100216 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-31 18:26:11 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) PROVIDE ON EQUIPMENT SCHEDULE WHICH HVAC SYSTEM IN | | | BUILDING WILL PROVIDE THE 1107 CFM TO INSURE OVERALL | | | BUILDING BALANCE IS POSITIVE. | | | (2) PROVIDE SEQUENCE OF OPERATION SHOWING SAID MAKE UP | | | AIR BUILDING HVAC SYTEM SHUTS DOWN WHEN HOOD IS IN | | | ALARM. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | | | | | | | | | | | | | | | | |
|