| | (1) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1. |
| | (2) PROVIDE LOCATION OF CONDENSER ON EXTERIOR OF BLDG. |
| | (3) CONFIRM INSULATION R VALUE. PLANS SHOW R8. DUCT |
| | INSULATION IS USUALLY R6. |
| | (4) BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. SEE ABOVE 107.2.1.4. |
| | (5) SHOW ON PLANS ALL BATH EXHUST. |
| | |
| | FLORIDA ENERGY CODE FBC 2014 |
| | |
| | (6) PROVIDE AHRI FOR EQUIPMENT ON PLANS. PLANS SHOW (2) |
| | 2 TON SYSTEMS. |
| | |
| | JORGE VALIDO |
| | WPB MECHANICAL INSPECTOR/PLANS EXAMINER |