| Plan Review Notes For Permit 16100211 |
| Permit Number |
16100211 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-28 13:24:34 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE SITE PLAN THAT SHOWS THE NEW GENERATOR AND | | | FUEL STORAGE TANK. TO INCLUDE DISTANCES FROM | | | SURROUNDING STRUCTURES AND TRAFFIC BARRIERS. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. PROVIDE COMPLETE RISER DIAGRAM FOR FUEL PIPING PER | | | WPB AMEND TO FBC 107.3.5.1.5(1)(9) | | | | | | 3. MANUFACTURE SPECIFICATION FOR STORAGE TANK. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. STRAPPING AND TIE DOWN DETAILS. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 4. MSDS SHEETS FO R DIESEL FUEL. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|