| Plan Review Notes For Permit 16100209 |
| Permit Number |
16100209 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-16 16:54:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED PLAN INDICATES EXISTING GENERATOR AND | | | DESCRIPTION OF WORK INDICATES LANDSCAPE SCREEN FOR | | | EXISTING GENERATOR. | | | | | | PLEASE CLARIFY THE SCOPE OF WORK, WHAT IS EXISTING, | | | NEW, REPLACED, OR PROPOSED, ETC. | | | | | | | | | 2) WHAT WILL THE GNERATOR SUPPLY POWER FOR, I.E. WILL | | | SUPPLY POWER FOR THE LIFE SAFETY SYSTEMS. | | | | | | PLEASE PROVIDE DETAILED SCOPE OF WORK WHICH MAY INCLUDE | | | COMPLIANCE WITH NFPA 110 EMERGENCY AND STANDBY POWER | | | SYSTEMS. | | | | | | | | | 3) PROVIDE DETAIL AND DIMENSIONS TO THE FIRE HYDRANT | | | AND NEAREST BUILDINGS. WHICH SIDE OF THE GENERATOR IS | | | THE EXHAUST LOCATED? | | | | | | | | | | | | 4) THE GENERATOR SHALL BE PROTECTED FROM VEHICULAR | | | TRAFFIC IMPACT, ARE POLLARDS BEING PROVIDED | | | | | | PLEASE CLARIFY. | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|