2016-10-19 18:53:46REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE ACTUAL ONE-LINE RISER DIAGRAM OF THE
 EXISTING ELECTRICAL SYSTEM, SHOW CONDUIT & WIRE SIZES,
 PANEL SCHEDULE, GROUNDING DETAIL, AND LOAD
 CALCULATIONS. FBC-107.3.5.3
  
 2] CLARIFY IF TRANSFER SWITCH IS SERVICE RATED AND THE
 ELECTRICAL VOLTAGE OF EQUIPMENT IS IT SINGLE PHASE OR
 THREE PHASE ? NEC 230.66
  
 3] NEW COMMENTS MAY BE NOTED UPON RE-REVIEW