| Plan Review Notes For Permit 16100209 |
| Permit Number |
16100209 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-19 18:53:46 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE ACTUAL ONE-LINE RISER DIAGRAM OF THE | | | EXISTING ELECTRICAL SYSTEM, SHOW CONDUIT & WIRE SIZES, | | | PANEL SCHEDULE, GROUNDING DETAIL, AND LOAD | | | CALCULATIONS. FBC-107.3.5.3 | | | | | | 2] CLARIFY IF TRANSFER SWITCH IS SERVICE RATED AND THE | | | ELECTRICAL VOLTAGE OF EQUIPMENT IS IT SINGLE PHASE OR | | | THREE PHASE ? NEC 230.66 | | | | | | 3] NEW COMMENTS MAY BE NOTED UPON RE-REVIEW |
|