| 2016-10-20 11:23:49 | OCP FOR PANEL H IS INCORRECT PER NEC 240.4(B)2 WHICH | | | INDICATES THE MOCP FOR THE FEEDER CONDUCTOR TO BE AT | | | 125A. SEE NEC 240.6 |
|