| Plan Review Notes For Permit 16100195 |
| Permit Number |
16100195 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-17 10:02:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. EXPOSURE CLASSIFICATION IS INCORRECT; THIS SHOULD BE | | | D (NOT B AS STATED ON PLAN), FBC 1609. | | | | | | 2. THE SIGN IS TO RESIST FLOOD LOADS TO 7.5', FBC 1622. | | | REVISE PLAN TO INDICATE COMPLIANCE. | | | | | | |
|