Notes
Date Text
2016-11-08 12:29:591) SHT. A8.04 - DETAIL # 10 - THE LOCATION OF OVERFLOW
 SCUPPERS IN THE PARAPET WALL SHALL COMPLY WITH 2014 FBC
 SEC. 1503.4.2.1.
 2) SHT. A8.03 - VANITY TOP PLAN- THERE IS A NOTE THAT
 READS "FIRST FLOOR ONLY." CLARIFY.
 3) SHT. P5.01 - RISER S/JS - THE RISER SHOWS THE MOP
 SINKS ON LEVELS #2 & #3 BUT RISER W/JS SHOWS THE WATER
 SUPPLY TO THE MOP SINKS REMOVED. CLARIFY.
 4) SHT. P1.01 - THE HUB DRAIN RECEIVING THE DISCHARGE
 FROM THE ELEVATOR SUMP SHALL BE EQUIPPED WITH A TRAP
 PRIMER PER 2014 FPC SEC.1002.4.
 5) A2.01 - REMOVE THE BACKGROUND DOTS FROM THE FLOOR
 PLAN. IT IS VERY DIFFICULT TO SE THE CLEAR FLOOR SPACE
 FOR THE FIXTURES AND COMPLIANCE WITH THE FHA.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  