| Date |
Text |
| 2016-12-13 13:50:04 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ANCHORING DETAIL ON SHEET M-1 SPECIFIES A 2 INCH |
| | CONCRETE PAD. M1305.1.4.1 GROUND CLEARANCE. EQUIPMENT |
| | AND APPLIANCES SUPPORTED FROM THE GROUND SHALL BE LEVEL |
| | AND FIRMLY SUPPORTED ON A CONCRETE SLAB OR OTHER |
| | APPROVED MATERIAL EXTENDING NOT LESS THAN 3 INCHES (76 |
| | MM) ABOVE THE ADJOINING GROUND. SUCH SUPPORT SHALL BE |
| | IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. APPLIANCES SUSPENDED FROM THE FLOOR SHALL |
| | HAVE A CLEARANCE OF NOT LESS THAN 6 INCHES (152 MM) |
| | FROM THE GROUND. |
| | |
| | 2) THE PLANS SHOW THE AIR HANDLER IN THE ATTIC AND IT |
| | APPEARS THAT THE DUCTWORK BLOCKS ACCESS FROM THE ACCESS |
| | OPENING TO THE APPLIANCE. M1305.1.3 APPLIANCES IN |
| | ATTICS. ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED |
| | WITH AN OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY |
| | LARGE ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, |
| | BUT NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES |
| | (559 MM) WIDE AND NOT MORE THAN 20 FEET (6096 MM) LONG |
| | MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM |
| | THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE |
| | CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 |
| | NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE |
| | SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES |
| | (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE |
| | APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS |
| | OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY |
| | 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW |
| | REMOVAL OF THE LARGEST APPLIANCE. |
| | |
| | 3) ONLY ONE OF THE ENERGY FORMS WAS SIGNED AND DATED BY |
| | THE OWNER. PLEASE HAVE THE OWNER SIGN AND DATE THE |
| | OTHER SET. FBC ENERGY R405-2014 |
| | |
| | |
| | |
| | |