Plan Review Notes
Plan Review Notes For Permit 16100185
Permit Number 16100185
Review Stop B
Sequence Number 2
Notes
Date Text
2016-12-13 09:00:37PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLAN SHEETS 1, 3 AND 4 DO NOT HAVE THE PROFESSIONAL
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE OR SEAL AS
 REQUIRED BY FAC 61G15-23.002.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 ASPHALT ROOF SHINGLES (NOA NO. 03-0219.04) EXPIRED IN
 2008. SUBMIT TWO SETS OF CURRENT PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC 107.3.4
  
 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 WINDOWS AND DOORS WERE NOT REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4
  
  
  
  
  
  
  