Plan Review Notes
Plan Review Notes For Permit 16100185
Permit Number 16100185
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-22 14:45:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WALLS OF THE STRUCTURE ARE NOT CLEARLY VISIBLE
 ON THE HVAC PLAN. FBC 107.2.1
  
 2) THE EQUIPMENT SCHEDULE ON SHEET M-1 DOES NOT MATCH
 THE ENERGY FORM OR LOAD CALCULATIONS. THE EER AND SEER
 ARE DIFFERENT AND THE MODEL NUMBER FOR THE AHU IS
 DIFFERENT.
  
 3) ONLY ONE COPY OF THE ENERGY AND LOAD CALCULATIONS
 WERE SUBMITTED. TWO SETS ARE REQUIRED. FBC 107.1
  
 4) THE OWNER / AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM R405-2014.
  
 5) PROVIDE AN EQUIPMENT ANCHORING DETAIL FOR THE
 MECHANICAL EQUIPMENT THAT IS LOCATED ON THE EXTERIOR OF
 THE STRUCTURE.FBC- M301.15
  
 5) THE AC EQUIPMENT SCHEDULE SPECIFIES THAT THE AIR
 HANDLER IS LOCATED IN A UTILITY CLOSET AND THE HVAC
 PLAN SHOWS IT MOUNTED HORIZONTALLY IN THE ATTIC. REVISE
 AS NECESSARY AND SHOW THE LOCATION OF THE A/H ON THE
 ARCHITECTURAL PLANS, AS WELL AS, THE HVAC PLANS. FBC
 107.2.1
  
 6) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 THE MECHANICAL PLANS SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
  
  