| 2016-10-19 11:23:16 | JOB PERMIT NUMBER: 16100185 |
| | JOB ADDRESS: 816 41 STREET |
| | WEST PALM BEACH FLORIDA |
| | DATE: OCTOBER 19, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. BELOW IS A LIST OF ITEMS NOTED. |
| | |
| | 1] IF THE SERVICE IS OVERHEAD PLEASE REMOVE THE LATERAL |
| | UNDERGROUND CONDUIT SHOWN AT THE METER IN THE RISER |
| | DIAGRAM. FBC-107 |
| | |
| | 2] ADD AN INTERSYSTEM BONDING TERMINAL TO THE GROUNDING |
| | DETAIL IN THE RISER DIAGRAM. FBC-R SEC E3609.3 |
| | |
| | 3] PROVIDE THE 200 AMP PANEL LOCATION ON THE FLOOR PLAN |
| | TO VERIFY WORK CLEARANCE, SHOW COMPLIANCE. FBC-R SEC |
| | E3405 |
| | |
| | 4] ADD A SMOKE ALARM OUTSIDE OF THE MASTER BED IN THE |
| | IMMEDIATE VICINITY OF THE SLEEPING AREA. FBC-R SEC |
| | 314.3 |
| | |
| | 5] ADD A WALL SWITCHED CONTROLLED LIGHTING OUTLET TO |
| | PROVIDE OUTDOOR ILLUMINATION FOR THE EXTERIOR DINING |
| | ROOM DOOR. FBC-R SEC E3903.3 |
| | |
| | 6] PROVIDE A GFCI SERVICE RECEPTACLE OUTLET WITHIN 25' |
| | OF THE OUTSIDE CONDENSER UNIT. FBC-R SEC E3901.11 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |