| 2016-11-22 16:24:34 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| | THE ROOFING MATERIALS, WINDOW/GLASS TYPES AND EXTERIOR |
| | DOOR TYPES. ONLY ONE PRODUCT APPROVAL WAS SUBMITTED FOR |
| | THE SINGLE HUNG WINDOWS AND NONE WERE SUBMITTED FOR THE |
| | DOORS OR ROOFING MATERIAL. |
| | |
| | 2) THE WALL SECTION AT THE MASTER BATHROOM SPECIFIES |
| | ONLY THE ONE LAYER OF FELT ON THE PAPER BACK LATH, |
| | WHICH DOES NOT COMPLY WITH R703.6.3 WATER-RESISTIVE |
| | BARRIERS. WATER-RESISTIVE BARRIERS SHALL BE INSTALLED |
| | AS REQUIRED IN SECTION R703.2 AND, WHERE APPLIED OVER |
| | WOOD-BASED SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| | VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| | EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| | INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| | THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| | AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| | R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| | BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| | |
| | |
| | |