| Date |
Text |
| 2017-02-03 09:58:22 | 2/03/2017 THE DESIGNER OF RECORD JAMES M STERGAS |
| | E-MAILED THE REQUIRED SOUND INSULATION TEST REPORTS |
| | ASTM E90 & ASTM E 492 STAMPED FLOORING PRODUCT |
| | APPROVALS. JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| 2017-01-30 14:16:31 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16100165 |
| | ADD: 255 EVERNIA ST. SUITE # 1519 |
| | CONT: ALL FLAGS CONSTRUCTION |
| | TEL: 561-312-7675 |
| | E-MAIL: STEVE @ ALLFLAGSCONSTRUCTION.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. JAN. 30/2017 |
| | ACTION: DENIED |
| | |
| | 1)2ND REQUEST. SUBMITTED THIS REVIEW IS A SALES |
| | BROCHURE HIGHLIGHTED IS THE ACTUAL TEST WE REQUIRE. |
| | TEST RAL IN98-41 RAFTL98-280 SHOULD SUPPLY THE REQUIRED |
| | IIC RATING TESTED TO ASTM E492 AND STC RATING TESTED TO |
| | ASTM E 90. SUBMIT TEST. |
| | |
| | SHEET A-1.01 NOTE 11 INDICATES THE REMOVAL OF ALL FLOOR |
| | TILE AND WOOD FLOORING AND INSULATION, THE PLANS DO NOT |
| | INDICATE WHAT MATERIAL IS TO BE RE-INSTALLED. THE |
| | STRAND IS DOCUMENTED AS HAVING 8 INCH CONCRETE FLOOR |
| | SLABS, EITHER TEST REPORTS FOR 6 INCH AND 8 INCH FLOOR |
| | SLABS ARE ACCEPTED. SEE SOUND INSULATION REQUIREMENTS |
| | LISTED BELOW. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |