| Plan Review Notes For Permit 16100163 |
| Permit Number |
16100163 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-24 15:15:44 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO'S (RED-LINED ON | | | PLANS) | | | | | | 1] NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL | | | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO | | | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP | | | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH | | | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE | | | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE | | | CONSIDERED ACCESSIBLE TO PEDESTRIANS | | | | | | 2] NEC 600.6 - PROVIDE DISCONNECT SWITCH AT SIGN | | | LOCATION. |
|