2017-01-30 17:55:21CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLAN SHOWING LOCATION OF MINI
 SPLIT AHU AND CONDENSER.
 (2) PROVIDE ALL INFORMATION ON WHO DREW PLANS AS PER
 107.2.1.
 (3) PROVIDE EQUIPMENT SCHEDULE ON FLOOR PLAN. ( INCLUDE
 BRAND, MODEL NUMBERS OF ALL EQUIPMENT, SEER, KW HEATER
 OR HP, TOTAL BTU).
  
 FLORIDA ENERGY CODE FBC 2014
  
 (4) FORMS R405-2014 MUST BE SIGNED AT PREPARED BY AND
 AT OWNER/AGENT. (SEE HIGHLIGHTED AREAS ON FORMS).
 (5) HEAT LOAD CALCULATIONS MUST BE FILLED OUT
 COMPLETELY. PROVIDE WHO PREPARED THE CALCULATIONS, DATE
 AND SIGNATURE.(SEE HIGHLIGHTED UPPER RIGHT HAND SIDE OF
 PAPER).
  