| 2017-01-05 13:55:00 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 |
| | |
| | SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED. 2014 |
| | FBC R 314, 315 |
| | |
| | HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES |
| | NEED TO BE RATED FOR INSULATION CONTACT. NEC 410.116; |
| | FBC R 4004 |
| | |
| | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH |
| | CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12 |
| | |
| | VERIFY RECEPTACLES ARE PROPERLY PLACED TO SERVICE ALL |
| | AREAS INCLUDING WALL SPACES TWO FEET OR MORE IN WIDTH. |
| | NEC 210.52 (A), FBC R E3901.2 |
| | |
| | CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE |
| | LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9 |
| | |
| | VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC |
| | 406.2; FBC R E4002.14 |
| | |
| | VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12; |
| | FBC R E3902.12 |
| | |
| | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND |
| | REAR ELEVATIONS. NEC 210.8 |
| | |
| | PROVIDE A DETAIL FOR THE TYPE AND SIZE OF CIRCUIT |
| | PROPOSED TO FEED THE NEW AIR CONDITIONING UNIT(S). FBC |
| | E3705.5, NEC 240.4 |
| | |
| | |