Plan Review Notes
Plan Review Notes For Permit 16100159
Permit Number 16100159
Review Stop E
Sequence Number 1
Notes
Date Text
2017-01-05 13:55:00PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED. 2014
 FBC R 314, 315
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT. NEC 410.116;
 FBC R 4004
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12
  
 VERIFY RECEPTACLES ARE PROPERLY PLACED TO SERVICE ALL
 AREAS INCLUDING WALL SPACES TWO FEET OR MORE IN WIDTH.
 NEC 210.52 (A), FBC R E3901.2
  
 CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE
 LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.2; FBC R E4002.14
  
 VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12;
 FBC R E3902.12
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE A DETAIL FOR THE TYPE AND SIZE OF CIRCUIT
 PROPOSED TO FEED THE NEW AIR CONDITIONING UNIT(S). FBC
 E3705.5, NEC 240.4
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  