| Plan Review Notes For Permit 16100154 |
| Permit Number |
16100154 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-01-24 14:43:52 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. ISOMETRIC DRAWING IS UNCLEAR AT WHAT POINT YOUR | | | REDUCING FROM 2LB TO .5LB SYSTEM. PLEASE SHOW REG. PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. PROVIDE TABLES USED TO SIZE THE SYSTEM. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. LOCATION OF THE POOL HEATER ON THE GAS RISER DOES | | | NOT MATCH FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 5.IT IS UNCLEAR ON THE RISER HOW THE BRANCH FOR THE | | | COOK TOP AND DRYER CONNECT TO THE MAIN RUN PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|