Plan Review Notes
Plan Review Notes For Permit 16100154
Permit Number 16100154
Review Stop G
Sequence Number 2
Notes
Date Text
2016-12-12 18:24:541ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS IT IS
 UNCLEAR AT WHAT POINT YOUR REDUCING FROM 2LB TO .5LB
 SYSTEM. PER FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. PROVIDE TABLES USED TO SIZE THE SYSTEM. PER WPB
 AMEND TO FBC 107.2.1
  
 4. PROVIDE FLOOR PLAN SHOWING GAS PIPING THE LOCATION
 OF THE POOL HEATER DOES NOT MATCH FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1