| Plan Review Notes For Permit 16100154 |
| Permit Number |
16100154 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-12 18:24:54 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS IT IS | | | UNCLEAR AT WHAT POINT YOUR REDUCING FROM 2LB TO .5LB | | | SYSTEM. PER FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. PROVIDE TABLES USED TO SIZE THE SYSTEM. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. PROVIDE FLOOR PLAN SHOWING GAS PIPING THE LOCATION | | | OF THE POOL HEATER DOES NOT MATCH FLOOR PLAN. PER WPB | | | AMEND TO FBC 107.2.1 |
|