Plan Review Notes
Plan Review Notes For Permit 16100154
Permit Number 16100154
Review Stop B
Sequence Number 2
Notes
Date Text
2016-12-06 19:03:11PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEETS A-3 AND A-4 THERE ARE ID TAGS FOR ROOF TO
 WALL CONNECTORS MARKED 1/A4 AND 2/A4, HOWEVER, THERE
 ARE NO CORRESPONDING DETAILS FOR THEM ON SHEET A-4.
 PLEASE CLARIFY. FBC 107.2.1
  
 2) THE ENERGY FORM 405 IS NOT COMPLETE AND IS NOT
 ACCURATE. THE ADDRESS OR OTHER IDENTIFICATION OF THE
 RESIDENCE IS MISSING. THE OWNER'S NAME AND BUILDER'S
 NAMES ARE MISSING. THE NAME OF THE PREPARER IS NOT
 LEGIBLE. FBC ENERGY R101.5.1.1.2 AND R103.2
  
 3) THE NUMBER OF OCCUPANTS FOR THE RESIDENCE IS
 SPECIFIED AS 4 (MAIN) AND 8 (BEDROOMS) FOR A TOTAL OF
 12 ON THE ENERGY FORM 405. IN THE EQUIPMENT SIZING
 CALCULATIONS THE NUMBER OF OCCUPANTS ARE SPECIFIED AS 6
 (MAIN) AND 8 (BEDROOMS) FOR A TOTAL OF 14. EXPLAIN HOW
 YOU ARE DETERMINING THE NUMBER OF OCCUPANTS AND WHY
 THEY ARE DIFFERENT OF FORM 405 AND THE SIZING
 CALCULATIONS. FBC 107.2.1
  
 4) THIS PERMIT IS FOR A SPECIFIC RESIDENCE THAT WILL BE
 BUILT ON A SPECIFIED LOT. IT IS NOT THE MASTER FOR A
 MODEL THAT WILL BE BUILT ON DIFFERENT LOTS WITH
 MULTIPLE ORIENTATIONS. THEREFORE, THE ENERGY
 CALCULATIONS ARE SITE SPECIFIC AND ARE NOT WORST CASE.
 USE THE ACTUAL DIRECTIONAL ORIENTATION OF THE BUILDING
 IN THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS. THERE SHOULD NOT BE ANY ROTATE ANGLE. FBC
 ENERGY R403.6.1 AND R405.4.2
  
  
  
  