| 2016-10-18 12:01:41 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: NEW SFR |
| | JOB ADDRESS: 71232 WINDING BAY LANE |
| | DESCRIPTION: NEW SFR |
| | MASTER PERMIT: 16100154 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS: THE CODE |
| | TO WHICH THE PROJECT IS BEING DESIGNED SHALL BE CLEARLY |
| | INDICATED ON THE DRAWINGS. |
| | 2. FBC-RE3902.12 HAS SPECIFIC REQUIREMENTS FOR |
| | ARC-FAULT PROTECTION AND THEY GO BEYOND THOSE INDICATED |
| | ON THE DRAWINGS. CORRECT BLOCK NOTE ACCORDINGLY. |
| | 3. FBC-RE4002.9 (NEC406.9(B)) IS THE APPLICABLE CODE |
| | SECTION WHICH REQUIRES THAT RECEPTACLES INSTALLED IN |
| | WET OR DAMP LOCATIONS BE LISTED WEATHER RESISTANT. |
| | CORRECT BLOCK NOTE ACCORDINGLY. |
| | 4. FBC-RE3905.8: BOXES USED FOR THE SOLE SUPPORT OF |
| | CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS |
| | SUITABLE FOR THE PURPOSE AND SUPPORT LOADS GREATER THAN |
| | 70 LBS. THIS SHALL BE ADDED TO THE BLOCK NOTES. |
| | 5. ACCORDING TO FBC REQUIREMENTS BATHROOM VENTILATION |
| | FOR THE CABANA BATH IS REQUIRED WHENEVER THE ROOM IS |
| | OCCUPIED AND THEREFORE SHALL GO ON WITH THE LIGHTS. THE |
| | EXHAUST FAN SHALL BE CONNECTED TO THE LIGHTING. |
| | 6. YOU INDICATED LIGHTING FOR THE ATTIC ACCESS ON THE |
| | PLANS. MAY I SUGGEST THAT THIS BE SWITCHED OUTSIDE THE |
| | ATTIC AND CONTROLLED WITH A SWITCH THAT HAS A PILOT SO |
| | AS TO INDICATE IF THE LIGHT IS ACCIDENTLY LEFT ON. |
| | FURTHERMORE, THERE SHALL BE LIGHTING AND A GFCI |
| | PROTECTED SERVICE OUTLET BY THE HVAC EQUIPMENT INSIDE |
| | THE ATTIC AS WELL. |
| | 7. ON THE RISER DIAGRAM YOU SHOW DOUBLE TAPPING AT THE |
| | METER SOCKET. UNLESS THE METER IS DOUBLE LUGGED THIS IS |
| | AGAINST CODE AND THEREFORE NOT ALLOWED. PROVIDE EITHER |
| | SPECS FOR THE PROPOSED DOUBLE LUGGED METER CAN OR A |
| | BLOCK NOTE ADDRESSING THIS ISSUE. |
| | 8. FBC-ER404.1: A MINIMUM OF 75% OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE OF THE |
| | HIGH-EFFICACY TYPE OR HAVE A MINIMUM OF 75% OF THE |
| | FIXTURES SHALL CONTAIN HIGH-EFFICACY LAMPS. |
| | 9. IN ADDITION TO THE ABOVE ENERGY CONSERVATION |
| | REQUIREMENT, LET ME SUGGEST THE USE OF ADDITIONAL |
| | SWITCHING (3 WAY ETC.) FOR THE MASTER BEDROOM ENTRY AND |
| | MASTER BEDROOM CORRIDOR. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |