2016-11-03 09:50:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE BUILDING CODE AND THE STANDARDS THAT ARE
 SPECIFIED ON SHEET C-1 ARE INCORRECT. PLEASE UPDATE TO
 THE 2014 FBC, ASTM C94-09, ASTM C90-11B, ASTM C270-08A,
 ASTM A615-09 AND ASTM A307-07B. 2014 FBC CHAPTER 46.
  
 2) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS
 REQUIRED TO HAVE A SELF CLOSING DEVICE. FBC-R 302.5.1
  
 3) THE TOTAL AREA SHOWN IN THE CALCULATION TABLE ON
 SHEET A-1 SHOULD BE 5593 SQUARE FEET. PLEASE CORRECT.
 FBC 107.2.1
  
 4) ON SHEET A-3 THERE ARE TAGS FOR 1/A4 AND THERE IS NO
 CORRESPONDING DETAIL FOR THEM ON SHEET A-4. PLEASE
 CLARIFY. FBC 107.2.1
  
 5) THE PLANS DO NOT SPECIFY THE INSULATION IN THE WALLS
 THAT ARE ADJACENT TO THE UNCONDITIONED GARAGE. FBC
 ENERGY CONSERVATION SECTION R303
  
 6) ON SHEET A-4 THE TRUSS ANCHOR IDENTIFICATION TAGS
 DID NOT PRINT DARK ENOUGH AND ARE BARELY LEGIBLE. THEY
 ARE NOT ACCEPTABLE TO BE SCANNED FOR PUBLIC RECORDS.
 FBC 107.2.1.4
  
 7) PRODUCT APPROVALS WERE SUBMITTED FOR SKYLIGHTS. SHOW
 THE SIZE AND LOCATION OF THE SKYLIGHT(S) ON THE PLANS.
 FBC-R 301.2.1
  
 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE 16'
 WIDE SECTIONAL GARAGE DOOR. THE ONE THAT WAS SUBMITTED
 IS LIMITED TO 9' WIDE DOORS.
  
 9) SUBMIT THE UPDATED 2014 CODE VERSION OF FL 10445 FOR
 THE FRONT DOORS. FBC 107.3.4
  
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 OUTDOOR BBQ AND ITS EXHAUST HOOD. FBC 107.2.1
  
 11) THE ENERGY COMPLIANCE FORM 405-10 THAT WAS
 SUBMITTED IS FOR THE 2010 FBC. SUBMIT TWO COPIES OF
 FORM 405-14 FOR THE 2014 FBC ENERGY CONSERVATION
 SECTION R405
  
 12) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 FORM 405-14. FBC ENERGY CONSERVATION SECTION R103.1.1.2
  
 13) THE ENERGY FORM LISTS A 50 GALLON GAS WATER HEATER
 AND THE PLANS SPECIFY TWO GAS TANKLESS WATER HEATERS.
 PLEASE CORRECT. FBC 107.2.1
  
 14) THE ENERGY CALCULATION FORMS STATE THAT THIS IS NOT
 A WORST CASE, THEN SPECIFIES A 90 DEGREE ROTATE ANGLE.
 THE ACTUAL ORIENTATION OF THE STRUCTURE ON THE LOT IS
 REQUIRED TO BE USED WHEN NOT USING WORST CASE. PLEASE
 CORRECT. FBC ENERGY CONSERVATION SECTION R405.4.2
  
 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  