Plan Review Notes
Plan Review Notes For Permit 16100126
Permit Number 16100126
Review Stop P
Sequence Number 1
Notes
Date Text
2016-11-08 11:09:361) SHT. A2.02 - THE ROOF PLAN IS ALMOST IMPOSSIBLE TO
 READ DUE TO THE BACKGROUND DOTS. SUBMIT A CLEAN ROOF
 PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. A8.04 - DETAIL # 10 - THE LOCATION OF OVERFLOW
 SCUPPERS IN THE PARAPET WALL SHALL COMPLY WITH 2014 FBC
 SEC. 1503.4.2.1.
 3) SHT. A8.03 - VANITY TOP PLAN- THERE IS A NOTE THAT
 READS "FIRST FLOOR ONLY." CLARIFY.
 4) SHT. A0.02 - THERE IS A CLOUDED NOTE AT THE TOP OF
 THE PAGE THAT READS " PROVIDE WOOD BLOCKING IN ALL
 FIRST FLOOR UNITS FOR FUTURE HANDICAP GRAB BARS". WOOD
 BLOCKING SHALL BE PROVIDED IN SLL UNITS PER THE FHA.
 5) SHTA2.01 - REMOVE THE BACKGROUND DOTS FROM THE FLOOR
 PLAN.IT IS EXTREMELY DIFFICULT TO SEE THE CLEAR FLOOR
 SPACE FOR THE FIXTURES AND COMPLIANCE WITH THE FHA.
 6) SHT. P2.01 - THE HUB DRAIN IN THE TRASH ROOM THAT
 RECEIVES THE DISCHARGE FROM THE ELEVATOR SUMP SHALL BE
 EQUIPPED WITH A TRAP PRIMER PER THE 2014 FBC-PLUMBING
 SEC.1002.4.
 7) SHT. P5.01 - RISER W/JS SHOWS THE WATER SUPPLY FOR
 MOP SINKS ON FLOORS 2 & 3 DELETED BUT THE MOP SINKS ARE
 STILL SHOWN ON RISER S/JS.CLARIFY.
 8) SUBMIT A NARRATIVE THAT CLEARLY DESCRIBES WHAT
 CHANGES HAVE BEEN MADE TO THE PLUMBING SYSTEMS AND
 WHERE THE CHANGES OCCUR.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW