| Plan Review Notes For Permit 16100126 |
| Permit Number |
16100126 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-08 11:09:36 | 1) SHT. A2.02 - THE ROOF PLAN IS ALMOST IMPOSSIBLE TO | | | READ DUE TO THE BACKGROUND DOTS. SUBMIT A CLEAN ROOF | | | PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHT. A8.04 - DETAIL # 10 - THE LOCATION OF OVERFLOW | | | SCUPPERS IN THE PARAPET WALL SHALL COMPLY WITH 2014 FBC | | | SEC. 1503.4.2.1. | | | 3) SHT. A8.03 - VANITY TOP PLAN- THERE IS A NOTE THAT | | | READS "FIRST FLOOR ONLY." CLARIFY. | | | 4) SHT. A0.02 - THERE IS A CLOUDED NOTE AT THE TOP OF | | | THE PAGE THAT READS " PROVIDE WOOD BLOCKING IN ALL | | | FIRST FLOOR UNITS FOR FUTURE HANDICAP GRAB BARS". WOOD | | | BLOCKING SHALL BE PROVIDED IN SLL UNITS PER THE FHA. | | | 5) SHTA2.01 - REMOVE THE BACKGROUND DOTS FROM THE FLOOR | | | PLAN.IT IS EXTREMELY DIFFICULT TO SEE THE CLEAR FLOOR | | | SPACE FOR THE FIXTURES AND COMPLIANCE WITH THE FHA. | | | 6) SHT. P2.01 - THE HUB DRAIN IN THE TRASH ROOM THAT | | | RECEIVES THE DISCHARGE FROM THE ELEVATOR SUMP SHALL BE | | | EQUIPPED WITH A TRAP PRIMER PER THE 2014 FBC-PLUMBING | | | SEC.1002.4. | | | 7) SHT. P5.01 - RISER W/JS SHOWS THE WATER SUPPLY FOR | | | MOP SINKS ON FLOORS 2 & 3 DELETED BUT THE MOP SINKS ARE | | | STILL SHOWN ON RISER S/JS.CLARIFY. | | | 8) SUBMIT A NARRATIVE THAT CLEARLY DESCRIBES WHAT | | | CHANGES HAVE BEEN MADE TO THE PLUMBING SYSTEMS AND | | | WHERE THE CHANGES OCCUR.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|