| Plan Review Notes For Permit 16100063 |
| Permit Number |
16100063 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-30 12:19:52 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ALL BUILDING COMMENTS HAVE BEEN ADDRESSED. | | | | | | THE NEW PLAN SHOWS THAT THE PROPOSED WORK IS IN SUITES | | | 5-6, BUT THE APPLICATION IS FOR SUITE 3. PLEASE SUBMIT | | | A NEW APPLICATION THROUGH THE FRONT COUNTER; THE | | | ADDRESS FOR THE PERMIT RECORD MUST ALSO BE CHANGED. FEE | | | MAY APPLY. | | | | | | WHEN THIS IS DONE, PLEASE ADVISE AND THE PLAN REVIEW | | | WILL BE PASSED. | | | | | | THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | | | | 1. A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED PRIOR TO C.O. | | | | | | 2. PRIOR TO INSTALLATION, SUBMIT A LETTER CLARIFYING | | | WIND DESIGN CRITERIA FOR THE ROOFTOP MECHANICAL | | | EQUIPMENT, DETAIL ON M2. THE WIND SPEED WAS PROVIDED | | | BUT EXPOSURE CLASSIFICATION WAS NOT. SEE FBC | | | 1603.1.4(3). THIS SITE REQUIRES A MINIMUM DESIGN | | | CRITERIA OF EXPOSURE C. | | | |
|