Plan Review Notes
Plan Review Notes For Permit 16100063
Permit Number 16100063
Review Stop M
Sequence Number 1
Notes
Date Text
2016-10-13 12:13:171ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100063
 10/13/16
  
 1) SHEET M2: THE VENTILATION RATE FOR THE STOCK AND
 PREPARATION ROOM SHALL BE CALCULATED AT- (10 PERSONS
 PER 1000 SQ. FT.) AT (5 CFM PER PERSON) AND (0.18 CFMS
 PER SQ. FT.). PLEASE CORRECT THE FRESH AIR CALCULATION.
  
 2) THE FUTURE CLEAN ROOM CANNOT BE PERMITTED UNDER THIS
 APPLICATION WITHOUT MORE SPECIFIC INFORMATION TO
 CLARIFY THE PROCESSES THAT WILL BE CONDUCTED IN THE
 ROOM; WHAT EQUIPMENT WILL BE IN THE ROOM, WHAT
 MATERIALS WILL BE STORED IN THE ROOM, HOW PARTICLE
 CONCENTRATION AND ENVIRONMENTAL CONDITIONS WILL BE
 CONTROLLED, AND HOW CROSS-CONTAMINATION WILL BE
 PREVENTED ETC. THE CURRENT LAYOUT PLAN SHOWS AIR
 COMMUNICATING FROM OTHER SPACES INTO THE CLEAN ROOM AND
 VICE-VERSA WHICH MAY BE PROHIBITED PER FDA OR OTHER
 REGULATORY GUIDELINES. VERY TYPICALLY HEPA FILTERS ARE
 USED FOR AIR DEVICES IN THESE TYPES OF ROOMS, HOWEVER
 NONE HAVE BEEN SPECIFIED. PLEASE REFER TO CHAPTER 18 OF
 THE ASHRAE HANDBOOK FOR MORE INFORMATION.
  
 3) M2: THE WIND LOAD DESGIN CRITERIA FOR ATTACHING THE
 RTU IS INCOMPLETE AND ALSO SPECIFIES AN INCORRECT WIND
 SPEED FOR WPB. REFER TO SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  