  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. BELOW IS A LIST OF ITEMS NOTED.
  
 1] LOW VOLTAGE SHALL BE UNDER A SEPARATE PERMIT
  
 2] ADD EMERGENCY LIGHTING TO THE MEANS OF EGRESS PATH
 INCLUDING THE EXIT DISCHARGE IN MAIN ROOM AREA, STOCK
 PREP ROOM, AND FUTURE CLEAN ROOM. THE ILLUMINATION
 LEVEL UNDER EMERGENCY POWER SHALL BE A MINIMUM 1'
 CANDLE AT THE WALKING SURFACE. FBC-1006
  
 3] THE LIGHTING IN THE MECHANICAL ROOM WHERE THE
 ELECTRICAL PANEL IS LOCATED SHALL NOT BE CONTROLLED BY
 AUTOMATIC MEANS. NEC 110.26(D)
  
 4] CLARIFY IF FUTURE CLEAN ROOM CONTAINS EXPLOSIVE
 CHEMICALS OR ACIDS THEREFORE CLASSIFIED AS A HAZARDOUS
 LOCATION PER NEC 500 ?
  
 5] PROVIDE A LIGHTING POWER DENSITY CHART TO
 DEMONSTRATE MAXIMUM ENERGY ALLOWANCES. SHOW COMPLIANCE
 USING THE TOTAL BUILDING OR SPACE BY SPACE METHODS WITH
 TRADE OFF PER FBC-E SEC C405.5.
  
 6] PROVIDE VOLTAGE DROP CALCULATIONS FOR FEEDERS OF
 PANEL A LOCATED IN SUITE #5. FEEDERS & CUSTOMER OWNED
 SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM OF 2%
 VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR A
 MAXIMUM OF 3% VOLTAGE DROP. ADD TO ELECT NOTES.
  
 7] ADD TO ELECT NOTES THE SOURCE OF POWER
 IDENTIFICATION MARK AT PANELBOARD PER NEC 408.4(B)
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011