| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | |
| | SHEET SE-100SECURITY CAMERA STILL LOCATED IN EXIT |
| | PASSAGEWAY #115. |
| | |
| | ORIGINAL COMMENT: 1ST FLOOR: ACCESS CONTROL CONDUIT, |
| | HARDWARE, ETC. AND SECURITY CAMERAS ARE NOT ESSENTIAL |
| | TO THE FUNCTION OF THE STAIR AND ARE NOT PERMITTED IN |
| | THE EXIT STAIRS OR EXIT PASSAGEWAY. PER NFPA 101 |
| | SECTION 7.1.3.2.1, PENETRATIONS INTO, AND OPENINGS |
| | THROUGH, AN EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO |
| | DOOR ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND |
| | CORRIDORS, REQUIRED EXIT DOOR OPENINGS, ELECTRICAL |
| | CONDUIT SERVING THE EXIT ENCLOSURE, DUCTWORK AND |
| | EQUIPMENT NECESSARY FOR INDEPENDENT STAIR |
| | PRESSURIZATION, WATER OR STEAM PIPING NECESSARY FOR THE |
| | HEATING OR COOLING OF THE EXIT ENCLOSURE, SPRINKLER |
| | PIPING, STANDPIPES, AND PENETRATIONS FOR FIRE ALARM |
| | CIRCUITS, WHERE THE CIRCUITS ARE INSTALLED IN METAL |
| | CONDUIT AND THE PENETRATIONS ARE PROTECTED. |
| | |
| | SHEET SE-106: DOOR HARDWARE DR20 AND DR21 ARE EQUIPPED |
| | WITH MAGNETIC LOCKS AND NO PUSH BUTTON OR OCCUPANCY |
| | SENSOR ON THE INTERIOR EGRESS SIDE OF THE DOOR. REFER |
| | TO ARCHITECTURAL LIFE SAFETY PLAN LS-7.0 WHEREBY THESE |
| | TWO DOORS ARE EXITING OCCUPANTS FROM INSIDE ROOM 701.01 |
| | THROUGH THE OUTSIDE POOL DECK. |
| | |