2016-10-12 11:53:02333 FERN STREET
 PERMIT #16100054
 MASTER #15031312
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1ST FLOOR: ACCESS CONTROL CONDUIT, HARDWARE, ETC. AND
 SECURITY CAMERAS ARE NOT ESSENTIAL TO THE FUNCTION OF
 THE STAIR AND ARE NOT PERMITTED IN THE EXIT STAIRS OR
 EXIT PASSAGEWAY. PER NFPA 101 SECTION 7.1.3.2.1,
 PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED TO DOOR ASSEMBLIES
 FROM NORMALLY OCCUPIED SPACES AND CORRIDORS, REQUIRED
 EXIT DOOR OPENINGS, ELECTRICAL CONDUIT SERVING THE EXIT
 ENCLOSURE, DUCTWORK AND EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION, WATER OR STEAM PIPING
 NECESSARY FOR THE HEATING OR COOLING OF THE EXIT
 ENCLOSURE, SPRINKLER PIPING, STANDPIPES, AND
 PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS ARE INSTALLED IN METAL CONDUIT AND THE
 PENETRATIONS ARE PROTECTED.
  
 GENERAL: PER NFPA 101 SECTION 7.2.1.6.2,
 ACCESS-CONTROLLED EGRESS DOORS ARE PERMITTED PROVIDED
 THAT ALL SEVEN OF THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 7TH FLOOR: ELEVATOR LOBBY MAG LOCK DOES NOT SHOW AN
 OCCUPANT SENSOR OR A PUSH TO EXIT BUTTON.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  
  