2017-02-13 09:11:563RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100033
 2/13/17
  
 1) ENERGY CONSERVATION COMPLIANCE: PLEASE SUBMIT THE
 FULL INPUT DATA REPORT AS REQUIRED- SEE PAGE 1,
 CHECKLIST ITEM 3 OF THE SUBMITTED ENERGY GAUGE
 COMPLIANCE REPORT.
  
 2) THE DESCRIPTION OF WORK ON THE APPLICATION MUST BE
 REVISED TO INDICATE INSTALLATION OF TWO 10-TON AC
 SYSTEMS, INCLUDING DUCTWORK, AND EXHAUST VENTILATION
 FOR THE TOILET ROOMS.
  
 3) PLEASE ADJUST THE VALUE OF $12,000 LISTED ON THE
 PERMIT APPLICATION TO AN ACCURATE VALUE THAT REFLECTS
 THE TOTAL SCOPE OF THE MECHANICAL WORK INCLUDING LABOR,
 MATERIALS, EQUIPMENT, AND DESIGN FEES- SECTION
 109.3VWPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  