Plan Review Notes
Plan Review Notes For Permit 16100033
Permit Number 16100033
Review Stop M
Sequence Number 2
Notes
Date Text
2016-10-28 14:25:002ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100033
 10/28/16
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PLEASE
 PROVIDE PLAN DESIGN CRITERIA- LIST THE CURRENT CODES
 AND STANDARDS THE PLANS ARE IN COMPLIANCE WITH.
  
 2) THE REVISED PLANS HAVE NOT BEEN SIGNED: ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5
 WPB AMENDMENTS TO THE FBC).
  
 3) THE REVISED PLAN SHOWS 4500 CFMS OF SUPPLY AIR,
 HOWEVER THE SUBMITTED MANUFACTURER'S SPECIFICATIONS
 INDICATE THE SYSTEM WILL PROVIDE A MAXIMUM OF 4000
 CFMS.
  
 4) THE REVISED PLAN INDICATES "THE UNIT WILL NOT HAVE A
 HEATER", HOWEVER HEAT IS REQUIRED FOR OCCUPIED SPACES.
 PLEASE SEE SECTION 309.1 FBC-14 MECHANICAL:
  
 SECTION 309 TEMPERATURE CONTROL 309.1 SPACE-HEATING
 SYSTEMS.
 INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE
 PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS
 CAPABLE OF MAINTAINING A MINIMUM INDOOR TEMPERATURE OF
 68?F (20?C) AT A POINT 3 FEET (914 MM) ABOVE FLOOR ON
 THE DESIGN HEATING DAY. THE INSTALLATION OF PORTABLE
 SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE
 WITH THIS SECTION.
  
 5) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE A
 DUCT SMOKE DETECTOR IN THE RETURN AIR SYSTEM PER
 SECTION 606.2.1.
  
 6) THE ENERGYGAUGE CONSERVATION COMPLIANCE SUBMITTAL
 MUST BEAR THE SIGNATURE OF THE OWNER/AGENT- SEE PAGE 3
 CERTIFICATIONS.
  
 7) THE SUBMITTED ENERGY FORM INDICATES A 3-TON SYSTEM
 THAT IS NOT SHOWN ON THE PLAN.
  
 8) THE SUBMITTED ENERGY FORM IS A ASHRAE 90.1 ENERGY
 COST BUDGET OPTION. INCLUDED IN THE MAIN DOCUMENT AND
 THE ATTACHED INPUT DATA REPORT ARE LIGHTING AND
 BUILDING CONSTRUCTION COMPONENTS DATA THAT MUST BE
 VERIFIED IN PLAN REVIEW AND INSPECTION. TO USE THIS
 OPTION PLEASE PROVIDE A PLAN THAT CORRELATES TO ALL
 DATA SHOWN IN THE DOCUMENTS- SEE SECTION 11.1.1 ASHRAE
 90.1- 2013.
  
 9) THE DESIGNER OR ENGINEER OF RECORD MUST COMPLETE THE
 MANDATORY REQUIRMENTS CHECKLIST ON PAGE OF THE ENERGY
 SUBMITTAL,
  
 10) THE AHU IS LOCATED IN A WAREHOUSE THAT INCLUDES A
 GRADE LEVEL GARAGE DOOR- PLEASE PROVIDE PROTECTION FROM
 VEHICULAR DAMAGE AS REQUIRED BY SECTION 303.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  