2016-10-04 10:56:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100033
 10/4/16
  
 1) PLEASE PROVIDE THE NAME OF THE PROPOSED BUSINESS ON
 THE PLAN.
  
 2) DESIGN CRITERIA: LIST THE CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT.
  
 3) PROVIDE COMPLETE EQUIPMENT SCHEDULES ON THE PLAN FOR
 THE AHU AND CONDENSER, AND SUBMIT AN AHRI CERTIFICATE.
 PLEASE NOTE THE PRODUCT SUBMITTAL DOESN'T INDICATE THE
 HEATING CAPACITY.
  
 4) A DUCT SMOKE DETECTOR IS REQUIRED TO BE INSTALLED IN
 THE RETURN AIR PLENUM PER SECTION 606.2.1.
  
 5) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SMACNA STANDARDS
  
 6) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 EXTERIOR CONDENSER- SECTION 310.15.
  
 7) THE PREVIOUSLY UNCONDITIONED WAREHOUSE NOW BEING
 CONDITIONED MUST BE BROUGHT INTO FULL COMPLIANCE WITH
 THE FLORIDA ENERGY CONSERVATION CODE AS REQUIRED IN
 SECTION C101.4.5. PLEASE SUBMIT DOCUMENTATION OF
 COMPLIANCE USING ONE OF THE PATHS OR METHODS LISTED
 UNDER SECTION C401.2.
  
 8) ADVISORY NOTE: THE MAIN PLANS FOR THE PROPOSED
 CHANGE OF OCCUPANCY HAVE NOT BEEN SUBMITTED FOR REVIEW
 AND APPROVAL. FURTHER COMMENTS MAY OCCUR UPON
 RESUBMITTAL OF CORRECTED PLANS.
  