| Plan Review Notes For Permit 16100012 |
| Permit Number |
16100012 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-11 11:19:45 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100012 | | | 10/11/16 | | | | | | 1) PROVIDE THE GAGE OF STAINLESS STEEL FOR THE GREASE | | | DUCT- SECTION 506.3.1.1. | | | | | | 2) PROVIDE PLAN AND ELEVATION VIEWS OF THE GREASE DUCT | | | SHOWING THE REQUIRED 18" CLEARANCES TO COMBUSTIBLES. | | | CLARIFY IF IF THE DUCT WILL BE WRAPPED WITH APPROVED | | | FIREWRAPPING AND HOW THE COMBUSTIBLE ROOF WILL BE | | | PROTECTED AT THE DUCT PENETRATION- SECTION 506.3.6. | | | | | | 3) PROVIDE THE HEIGHT OF EXHAUST FAN DISCHARGE OPENING | | | ABOVE THE ROOF SURFACE- 506.3.13.1. | | | | | | 4) PROVIDE A ROOF PLAN SHOWING THE REQUIRED CLEARANCES | | | FOR THE EXHAUST TERMINATION AS REQUIRED IN SECTION | | | 506.3.13.3 | | | | | | 5) PROVIDE ENGINEERING FOR ANCHORING THE FANS AND CURBS | | | TO THE ROOF STRUCTURE- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|