| Plan Review Notes For Permit 16100008 |
| Permit Number |
16100008 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-31 15:43:06 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100008 | | | 10/31/16 | | | | | | 1) THE REQUESTED SPECS FOR THE PIZZA OVEN THAT INDICATE | | | COMPLIANCE WITH THE ANSI Z21.1, ANSI Z21.58, OR ANSI | | | Z83.11 WERE NOT SUBMITTED. | | | | | | 2) PROVIDE DOCUMENTATION FROM THE MANUFACTURER OF THE | | | PIZZA OVEN THAT STATES FIRE SUPPRESSION IS NOT | | | REQUIRED. | | | | | | 3) INDICATE ON THE PLAN WHICH OF THE 5 DUCT MODELS IN | | | THE SUBMITTED SPECIFICATIONS WILL BE INSTALLED- DW, | | | DW-2R, DW 2R TYPE HT, DW-3R, OR DW-3Z. THE REVISED PLAN | | | APPEARS TO INDICATE THE DUCT MAKING A ZERO-CLEARANCE | | | PENETRATION OF THE COMBUSTIBLE ROOF SURFACE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|