| Notes |
| Date |
Text |
| 2016-10-04 12:22:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100003 | | | 10/4/16 | | | | | | 1) XVENT BOX SUBMITTALS: PLEASE REVIEW SECTION 501.3,2 | | | PRINTED BELOW AND VERIFY COMPLIANCE. | | | | | | 501.3.2 EXHAUST OPENING PROTECTION. | | | EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE | | | PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR | | | GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL | | | BE SIZED NOT LESS THAN 1/4 INCH (6 MM) AND NOT LARGER | | | THAN 1/2 INCH (13 MM). OPENINGS SHALL BE PROTECTED | | | AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT | | | EXHAUST OPENINGS IN STRUCTURES LOCATED IN | | | HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA | | | BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA | | | STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR | | | WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL | | | OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|