| 2016-11-04 08:15:04 | 1ST REVIEW FBC-2014 RESIDENTIAL, ENERGY CONSERVATION |
| | PERMIT #16091117 |
| | 10/31/16 |
| | |
| | 1) THE AC PLAN ON A-2 AND THE AC SIZING CALCULATIONS |
| | MUST BEAR THE SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC. |
| | PLEASE NOTE THAT ONLY FL. LICENSED DESIGN PROFESSIONALS |
| | OR INSTALLING AC CONTRACTORS ARE PERMITTED TO DRAW AC |
| | PLANS PER SECTION 105.3.1.2 |
| | |
| | 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN- |
| | SECTION R403.6.1 FBC-14 ENERGY CONSERVATION |
| | |
| | 3) INDICATE THE BRANCH DUCT AND DIFFUSER SIZES- ONLY |
| | THE MAIN TRUCKS HAVE BEEN SIZED- SECTION 107.3.5.1.4. |
| | |
| | 4) SHOW THE CONDENSATE PIPING RUN AND DISPOSAL |
| | LOCATION- SECTION M1411.3 FBC- RESIDENTIAL. |
| | |
| | 5) SHOW THE DRYER VENT RUN AND TERMINATION LOCATION. |
| | INDICATE THE TYPE AND SIZE OF VENT AND VENT CAP- |
| | SECTION M1502. |
| | |
| | 6) INDICATE THE TYPE OF KITCHEN EXHAUST TO BE INSTALLED |
| | AND PROVIDE SPECIFICATIONS- REFER TO SECTION M1503- |
| | M1507 FBC-RESIDENTIAL. |
| | |
| | 7) PROVIDE A NUMBER FOR EACH BEDROOM- 1,2,3, OR 4 ON |
| | THE FLOOR PLAN SO THE PLAN MATCHES THE MANUAL J |
| | WORKSHEETS. |
| | |
| | 8) THE DIRECTIONAL ORIENTATIONS SHOWN IN THE MANUAL J |
| | WORKSHEETS FOR WINDOWS AND DOORS DO NOT APPEAR TO MATCH |
| | THEIR DIRECTIONAL ORIENTATIONS ON THE PLAN. |
| | |
| | 9) SHOW THE LOCATION OF THE AC CONDENSER AND PROVIDE |
| | DETAILS FOR INSTALLATION OF THE MOUNTING PAD AND |
| | ANCHORING THE CONDENSER- SECTIONS M1305.1.4.1, AND |
| | M1401.4. |
| | |
| | 10) ENERGY FORM R405-2014: |
| | |
| | A) PLEASE FILL IN ALL THE REQUESTED INFORMATION AT THE |
| | TOP OF PAGE 1- OWNER, BUILDER NAME, PERMIT OFFICE, |
| | PERMIT NUMBER, JURISDICTION. CORRECT THE CLIMATE ZONE 2 |
| | DESIGNATION TO 1A PER TABLE R301.1. |
| | |
| | B) THE SUBMITTED ENERGY FORM IS INDICATING A "WORST |
| | CASE" COMPLIANCE, HOWEVER A WORST CASE COMPLIANCE IS |
| | USED FOR MODEL HOMES AND NOT FOR INDIVIDUAL RESIDENCES |
| | AS NOTED IN SECTION R405.4.2 EXCEPTION, ENERGY |
| | CONSERVATION. PLEASE CORRECT PAGE 1 AND PAGE 4, AND |
| | REVISE THE WINDOW ORIENTATIONS SO THEY MATCH WITH THE |
| | ORIENTATIONS TO BE SHOWN ON THE CORRECTED MANUAL J |
| | WORKSHEETS. |
| | |
| | C) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION |
| | CHECKLIST AND ALL REQUIRED INFORMATION AT THE TOP OF |
| | THE PAGE- OWNER, BUILDER NAME, PERMIT OFFICE, PERMIT |
| | NUMBER, JURISDICTION. |
| | |
| | 11) PLEASE SUBMIT TWO SETS OF CORRECTED PLANS PER |
| | SECTION 107.1 WPB AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE. |
| | |