| 2016-10-18 09:37:07 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND |
| | LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC |
| | RATINGS. FBC 107.3.5 |
| | 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS |
| | FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5 |
| | 3. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI |
| | DEVICE. FBC RES E3902.3 |
| | 4. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE |
| | PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE |
| | HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET |
| | THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2 |
| | ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5 |
| | 5. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT |
| | RECEPTACLE THROUGHOUT. FBC RES E4002.14 |
| | 6. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO |
| | INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. |
| | 7. ELECTRICAL SHEET TO BE SIGNED AND SEALED BY DESIGNER |
| | OF RECORD. FBC 107.3.5 |
| | 8. EXTERIOR RECEPTACLES TO BE GFCI PROTECTED, LABEL AT |
| | THE PANEL CIRCUIT #26 FBC RES E3902.3 |
| | 9. ADDRESS SPACING FOR COUNTERTOP RECEPTACLES IN |
| | KITCHEN PER FBC RES E3901.4 LEFT OF RANGE. |
| | 10. SHOW LIGHTING OUTLET AT THE ATTIC ACCESS LOCATION |
| | PER FBC RES E3903.4 SHOW ATTIC LOCATION |
| | 11. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC |
| | RES E3902.12 |
| | 12. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | QUESTIONS OR CONCERNS. |
| | |