Plan Review Notes
Plan Review Notes For Permit 16091103
Permit Number 16091103
Review Stop E
Sequence Number 1
Notes
Date Text
2016-10-03 13:43:49REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] DESCRIBE THE EXTENT OF THE ELECTRICAL SCOPE OF WORK,
 PLANS MUST BE SIGNED WITH THE JOB ADDRESS, APPLICABLE
 CODES, AND THE PERSON RESPONSIBLE FOR THE DESIGN. FBC
 107 ( IF THE ELECTRICAL WORK IS BEING PERFORMED UNDER A
 SEPERATE PERNIT PLEASE REFERENCE THAT PERMIT # )
  
 2] SMOKE ALARMS AND CARBON MONOXIODE ALARMS REQUIRED
 PER FBC-R 314 & 315. ( A NOTE WILL SUFFICE IF EXISTING
 OTHERWISE SHOW LOCATION ON FLOOR PLANS )
  
 3] ANY NEWLY MODIFIED CIRCUIT IN AREAS SPECIFIED IN NEC
 210.52 WILL BE SUBJECT TO ARC-FAULT PROTECTION IN
 ACCORDANCE WITH NEC 210.12(B).