| Plan Review Notes For Permit 16091062 |
| Permit Number |
16091062 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-03 06:42:42 | 1)SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE DRYER | | | AND THE RANGE PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 | | | OR 2014 FBC-RES. SEC. G 2407. | | | 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, AND FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR | | | 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE | | | LISTED AND LABELED. THE INSTALLATION MANUALS FOR ALL | | | GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME | | | OF INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | 3) SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE | | | WINDOWS AND DOORS FROM THE TANKLESS WATER HEATER. THE | | | LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH | | | THE MANUFACTURER'S INSTALLATION INSTRUCTONS. | | | 4) SHOW THE TYPE OF PIPE AND PIPE SIZE ON THE | | | CONSUMER'S SIDE OF THE GAS METER. | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|