Plan Review Notes
Plan Review Notes For Permit 16091004
Permit Number 16091004
Review Stop P
Sequence Number 1
Notes
Date Text
2016-11-08 10:26:121) SHT. A2.02 - THE ROOF PLAN IS ALMOST IMPOSSIBLE TO
 READ DUE TO THE BACKGROUND DOTS. SUBMIT A CLEAN ROOF
 PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. A8.04 - DETAIL # 10 - THE LOCATION OF OVERFLOW
 SCUPPERS IN THE PARAPET WALL SHALL COMPLY WITH 2014 FBC
 SEC. 1503.4.2.1.
 3) SHT. A8.03 - VANITY TOP PLAN- THERE IS A NOTE THAT
 READS "FIRST FLOOR ONLY." CLARIFY.
 4) SHT. A0.02 - THERE IS A CLOUDED NOTE AT THE TOP OF
 THE PAGE THAT READS " PROVIDE WOOD BLOCKING IN ALL
 FIRST FLOOR FOR FUTURE HANDICAP GRAB BARS". WOOD
 BLOCKING SHALL BE PROVIDED IN SLL UNITS PER THE FHA.
 5) SHT. P5.01 - RISER S/JS - THE RISER STILL SHOWS THE
 MOP SINKS ON LEVELS #2 & #3 BUT THE NARRATIVE STATES
 THESE MOP SINKS ARE TO BE DELETED. CLARIFY.
 6) SHT. P1.01 - THE HUB DRAIN RECEIVING THE DISCHARGE
 FROM THE ELEVATOR SUMP SHALL BE EQUIPPED WITH A TRAP
 PRIMER PER 2014 FPC SEC.1002.4.
 7) A2.01 - REMOVE THE BACKGROUND DOTS FROM THE FLOOR
 PLAN. IT IS VERY DIFFICULT TO SE THE CLEAR FLOOR SPACE
 FOR THE FIXTURES AND COMPLIANCE WITH THE FHA.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  