| 2016-10-03 11:24:26 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1] C/U DISCONNECT IS LOCATED BEHIND THE UNIT, SHOW | | | PROPER WORKING CLEARANCE. FBC-R_E3405 | | | | | | 2] PROVIDE LOCATION OF ALL SMOKE ALARMS IN THE ELECT | | | FLOOR PLAN AND DUE TO THE GARAGE CARBON MONOXIODE | | | ALARMS ARE REQUIRED OUTSIDE OF EACH BEDROOM. FBC 314 & | | | 315. | | | | | | 3] CLARIFY 220 V OUTLET LOCATED BY THE KITCHEN SINK ? | | | ARE THESE INTENTED TO BE COUNTER-TOP GFCI RECEPTACLES ? | | | | | | 4] PROVIDE WIRE AND CONDUIT SIZE FOR THE NEW 125 AMP | | | PANEL ON THE RISER DIAGRAM. FBC 107 |
|