| 2016-11-01 07:09:43 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE EXISTING SINGLE FAMILY STRUCTURE HAS A |
| | IMPROVEMENT VALUE OF MORE THAN $300,000.00. SECTION |
| | 708.8 OF THE FBC EXISTING BUILDING REQUIRES: |
| | (A) ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS |
| | REQUIRED BY SECTION 708.8.1. |
| | (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION |
| | SHALL NOT BE REQUIRED BEYOND A 15-PERCENT INCREASE IN |
| | THE COST OF REROOFING. |
| | SHOW HOW THIS WILL BE ACCOMPLISHED. |
| | THE BUILDING CODE DOES NOT HAVE A PROVISION THAT ALLOWS |
| | THE OWNER TO CHOSE NOT TO COMPLY WITH A CODE |
| | REQUIREMENT. |
| | 2016 FLORIDA STATUTES 553.844 WINDSTORM LOSS |
| | MITIGATION; REQUIREMENTS FOR ROOFS AND OPENING |
| | PROTECTION. |
| | 3. PRESCRIPTIVE TECHNIQUES FOR IMPROVEMENT OF |
| | ROOF-TO-WALL CONNECTIONS. THE LEGISLATURE RECOGNIZES |
| | THAT THE COST OF RETROFITTING EXISTING BUILDINGS TO |
| | MEET THE CODE REQUIREMENTS FOR NEW CONSTRUCTION IN THIS |
| | REGARD MAY EXCEED THE PRACTICAL BENEFIT TO BE ATTAINED. |
| | THE LEGISLATURE INTENDS FOR THE COMMISSION TO PROVIDE |
| | FOR THE INTEGRATION OF ALTERNATE, LOWER-COST MEANS THAT |
| | MAY BE EMPLOYED TO RETROFIT EXISTING BUILDINGS THAT ARE |
| | NOT OTHERWISE REQUIRED TO COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE FOR NEW CONSTRUCTION SO |
| | THAT THE COST OF SUCH IMPROVEMENTS DOES NOT EXCEED |
| | APPROXIMATELY 15 PERCENT OF THE COST OF REROOFING. |
| | ROOF-TO-WALL CONNECTIONS SHALL NOT BE REQUIRED UNLESS |
| | EVALUATION AND INSTALLATION OF CONNECTIONS AT GABLE |
| | ENDS OR ALL CORNERS CAN BE COMPLETED FOR 15 PERCENT OF |
| | THE COST OF ROOF REPLACEMENT. FOR HOUSES THAT HAVE BOTH |
| | HIP AND GABLE ROOF ENDS, THE PRIORITY SHALL BE TO |
| | RETROFIT THE GABLE END ROOF-TO-WALL CONNECTIONS UNLESS |
| | THE WIDTH OF THE HIP IS MORE THAN 1.5 TIMES GREATER |
| | THAN THE WIDTH OF THE GABLE END. PRIORITY SHALL BE |
| | GIVEN TO CONNECTING THE CORNERS OF ROOFS TO WALLS BELOW |
| | THE LOCATIONS AT WHICH THE SPANS OF THE ROOFING MEMBERS |
| | ARE GREATEST; |
| | 4.?STRENGTHENING OR CORRECTING ROOF-DECKING ATTACHMENTS |
| | AND FASTENERS DURING REROOFING; AND |
| | 5.?ADDING OR STRENGTHENING OPENING PROTECTIONS. |
| | |
| | |